SENSOR FOR ELECTROMAGNETIC FLOW METER – MANUAL

7

ESENS_FULLBORE_05.doc

ISOIL

METALLIC RING

INSULATING GASKET

INSULATING

BUSH

METALLIC

RING

INSULATING GASKET

If the sensor must be install

in the piping with a chatode

protection, is necessary:

If the sensor has to be mounted on a

pipe made of an insulating material

is necessary:

Sensors with ground socket

on the connection box

- Install two metallic ring between

the sensor flanges and the counter

flanges of the pipe line or:

- Use a sensor with the additional

grounding electrode

- using insulating bushes to isolate

the bolts

- Grounding metallic rings should be

provided to ground the liquid using

insulating gasket between the rings

- IMPORTANT :

The ripple of DC power source used

for cathodic protection

shall be = 0

Wafer sensors

Flanged sensors

For correct operation of the meter, it is NECESSARY that the sensor and the
liquid are equipotential, so ALWAYS connect the sensor and converter to

ground:

o

Grounding with metallic pipe

o

Grounding with insulating pipe

o

o

Grounding when there is a

cathodic protection over the pipe

GROUNDING INSTRUCTIONS







































-

IMPORTANT :

The ripple of DC power
source used for
cathodic protection
must be 0.

If the sensor is mounted on a pipe made of an insulating material,
do one of the following:

-

Install a metallic ring between the sensor flange and the

pipe counter flange,

-

or use a sensor with the additional grounding electrode.

If the sensor is mounted on a pipe with a cathode protection, do the
following:

-

use insulating bushes to isolate the bolts,

-

insert insulating gaskets on both sides of the rings to

ground the metallic rings and hence the liquid.