InstallationandWiring

Type 8071

Warning

risk of injury due to non-conforming installation.
• The electrical and fluid installation can only be carried out by

qualified and skilled staff with the appropriate tools.

• Install the appropriate security devices (correctly dimensioned

fuse and/or circuit breaker).

risk of injury due to unintentional switch on of power supply
or uncontrolled restarting of the installation.
• Take appropriate measures to avoid unintentional activation of

the installation.

• Guarantee a set or controlled restarting of the process sub-

sequent to the installation of the device.

7.2.

installation instructions

note

risk of damaging the device if it is subjected to mechanical
stress.
• Use flexible hoses.

note

the oval rotors may be damaged if particles with dia-
meter > 75 µm go into the fitting.
• Install a strainer of 75 µm upstream and as close as possible to

the device.

Install a by-pass line on your installation to service the device
and the strainer without stopping the process (see Fig. 4).

valve

direction of flow

filter

8071

Fig. 4: Installation of a by-pass line

Install the device onto the pipe so that the shafts of the rotors
are in a horizontal plane.

Seal the external threads of the fitting with a product com-
patible with the materials from which the device housing
and the pipe are made.

Screw the device onto the pipe.