Flow element installation, Wiring installation – Fluid Components International FR73B Complete Manual User Manual

Page 3

Advertising
background image

FR78B Flow Switch/Monitor

FLUID COMPONENTS INTERNATIONAL LLC

This page is subject to proprietary rights statement on last page

3

Doc. No. 06EN003281 Rev. A

Required Materials

Appropriate wire, cable, and conduit.

Note:

Potting Y's for all the interconnecting wires are recommended when installing the instrument's control circuit
in an enclosure. Other requirements may vary based on local wiring codes.

Pre-Installation Procedure

Warning:

Only qualified personnel should install this instrument. Install and follow safety procedures in accordance

with the current National Electrical Code. Ensure that power is off during installation. Any instances where

power is applied to the instrument will be noted in this manual. Where the instructions call for the use of

electrical current, the operator assumes all responsibility for conformance to safety standards and practices.

Caution:

Damage resulting from moisture penetration of the local or remote (optional) enclosure is not covered by

product warranty.

Verify Serial Numbers

Verify that the flow element serial number matches the control circuit serial number.

Verify Installation Location

Prepare the vessel for installation, or inspect the already prepared location to ensure that the instrument will fit into the system.

The location that should have been prepared at the time of order should be at least 20 pipe diameters downstream and 10 pipe

diameters upstream from any bends or interference in the process pipe or duct to achieve the greatest accuracy.

Flow Element Installation

Verify the correct orientation of the flow element. Install the flow element in-line with the process media flow. See the specifications

on page 2 for the various process connections available. See Appendix A, Figure 8, for the dimensions and orientation of the flow
element. Vertical mounting is as shown in Figure 8. Horizontal mounting is to have the flow arrow positioned up, or on top, and in the
direction of flow.

Wiring Installation

Conduit Routing

All socket and/or terminal block connections are to be made through openings in the remote enclosure if used. FCI strongly

recommends that all electrical cables be run through an appropriate conduit for the protection of the instrument and personnel if a

remote enclosure is used.

Protection of the control circuit from moisture is an important consideration. Keep the entry of the conduit into the enclosure in

the downward direction so condensed moisture that collects in the conduit will not drain into the enclosure. In addition, FCI

recommends sealing off the conduit with a potting Y or other sealing method to prevent moisture from entering the remote

enclosure if used.

Minimum Wire Size

Table 1 shows the smallest (maximum AWG number) copper wire that is to be used in the electrical cables for connecting the

instrument to the customer alarms and power. Use a lower gauge of wire for less of a voltage drop. Contact FCI concerning

greater distances than those listed in the table.

Table 1 - Interconnecting Cable Size (AWG)

M axim um Distance for AW G

Connection

10 ft.

(3m )

50 ft.

(15m )

100 ft.

(31m )

250 ft.

(76m )

500 ft.

(152m )

1000 ft.

(305m )

Input Pow er

22 22 22 20 18 16

Relay

24 22 20 16 12 10

Advertising