Fluid Components International CMF Series Manual Technical Data User Manual

Page 3

Advertising
background image

Technical data

FlexCOR

ä

Model CMF Series

8

Fluid Components Intl

Document 06EN003327 Rev. -

Measurement of

Mass flow [lb/min / kg/s], volume flow [gpm, l/s], fraction [%],

°Brix, density [kg/m

3

], temperature [°F,

°C]

Current output

Current

0-20 mA or 4-20 mA

Load

< 800 ohm

Time constant

0-30 s adjustable

Digital output

Frequency

0-10 kHz, 50% duty cycle

Time constant

0-30 s adjustable

Active

24 V d.c., 30 mA,

1 KW

£ R

load

£ 10 KW, short-circuit-protected

Passive

3-30 V d.c., max. 110 mA,

1 KW

£ R

load

£ 10 KW

Relay

Type

Change-over relay

Load

42 V / 2 A peak

Functionality

Error level, error number, limit, direction

Digital input

11-30 V d.c., Ri = 13.6 K

W

Functionality

Start/hold/continue batch, zero point adjust, reset totalizer 1/2, force output, freeze output

Galvanic isolation

All inputs and outputs are galvanically isolated, isolation voltage 500 volts

Cut-off

Low-flow

0-9.9% of maximum flow

Limit function

Mass flow, volume flow, fraction, density, sensor temperature

Totalizer

Two eight-digit counters for forward, net or reverse flow

Display

Background illumination with alphanumerical text, 3 × 20 characters to indicate flow rate, totalized
values, settings and faults.
Operation: -4 to 122°F (

-20 to +50°C), max. rel. humidity 80% to 87°F (31°C) decreasing to 50% at 104°F

(40

°C) according to UL 3101.

During storage: -40 to 158°F (-40 to +70

°C) (Humidity max. 95%)

Communication

Prepared for client mounted add-on modules

Enclosure

Material

Standard 19" insert of aluminium/steel (DIN 41494)

Dimensions

Width:

21 TE

Height:

3 HE

Rating

IP 20 to IEC 529 and DIN 40050

Load

Version: 1 G, 1-800 Hz sinusoidal in all directions, to IEC 68-2-6

EMC performance

Emission

EN 50081-1 (Light industry)

Immunity

EN 50082-2 (Industry)

Namur

Within the value limits according to "Allgemeine Anforderung" with error criteria A in accordance with
NE 21

Supply voltage

24 V version

230 V version

Supply

24 V d.c./a.c., 50-60 Hz

115/230 V a.c., 50-60 Hz

Fluctation

24 V d.c.,

-25 to 25%

+10 to -10%

24 V a.c.,

-16 to 25%

Power consumption

10 W

26 VA

Fuse

230 V version: T400 mA, T 250V (IEC 127) - Not to be changed by user
24 V version: T1A, T 250V (IEC 127) - Not to be changed by user

Evironment

Environmental conditions acc. to UL 3101:

Indoor use
Altitude up to 6500 FT. (2000 m)
POLLUTION DEGREE 2

Ex approval

[EEx ia] IIC, DEMKO Ex 99E.125729X

Mass Flowmeter 19" IP 20

2.2.2 Mass Flowmeter 19" IP 20

The Transmitter is also available in the 19" version with outputs increased to 3 current outputs, 2 digital
outputs, 2 relay outputs, 1 digital input
Other data is identical to the above

Transmitter 19" insert
version with extended
outputs

2.2.3

Transmitter 19" IP 20 with extended outputs