Fluid Components International ST98 Profibus C101-U Module User Manual

Page 4

Advertising
background image

DOCUMENT NUMBER

06EN003344

SUBJECT

Users Guide – ST98 Profibus

CAGE CODE

64818

DATE

03/27/03

SECTION

PAGE

1 of 3

REVISION

A


NOTICE OF PROPRIETARY RIGHTS: THIS DOCUMENT CONTAINS CONFIDENTIAL TECHNICAL DATA, INCLUDING TRADE SECRETS AND

PROPRIETARY INFORMATION WHICH ARE THE PROPERTY OF FLUID COMPONENTS INTL (FCI)

1.0 SCOPE

This document is a supplement to instructions that use the ISM 101-C Profibus-DP communication
module. It provides information on the instruction set used by the module. The ISM 101-C module
converts the current output of an FCI instrument into a Profibus –DP signal.

2.0 APPLICABLILITY

The instructions and information found in this document are applicable to the ST98 with the ISM 101-
C Profibus module.

3.0 INSTALLATION


3.1 PROFIBUS CONNECTIONS

The ST98 PROFIBUS data transfer is based on the RS485 Standard and EN50170. When

planning the Installation it is recommended that the physical regulation for PROFIBUS equipment
as described in EN50170 be followed.

See Figure below for recommended connection to PROFIBUS network.




A Line


B line
















PROFIBUS CABLE


The ST98 with the E.BLOXX PROFIBUS module has no integrated terminating resistors . An
external termination resistor network needs to be added at the end of segment is the ST98 is the
last instrument in the segment.




Advertising