Service transducer block parameters – Fluid Components International ST100 Series PROFIBUS PA User Manual

Page 10

Advertising
background image

ST100 Series Profibus PA

6

Fluid Components International LLC

REL. INDEX

PARAMETER

SLOT

INDEX

DATA TYPE (LENGTH)

STORE SIZE READ/WRITE

8

FLOW_TYPE

10

24

UNSIGNED 8

D

1

RW

9

TOTALIZER_STATE

10

25

UNSIGNED 8

D

4

RW

10

PLENUM_SIZE_VALUE1

10

26

FLOAT

D

4

RW

11

PLENUM_SIZE_VALUE2

10

27

FLOAT

D

4

RW

12

WRITE_PROTECT_MODE

10

28

UNSIGNED 8

D

1

RW

13

FACTORY_RESTORE

10

29

UNSIGNED 8

D

1

RW

14

DEVICE_CO

10

30

OCTETSTRING

D

10

R

15

DEVICE_SERIAL_NUM

10

31

OCTETSTRING

D

10

R

16

DEVICE_SFTWR_VER

10

32

OCTETSTRING

D

4

R

17

SENSORS_BANK_1

10

33

FLOAT

D

48

R

Service Transducer Block Parameters
The Service Transducer Block is a manufacturer specific block that contains ST100 configuration and setup parameters so that some configuration can

be done from the control room through PROFIBUS PA. It facilitates the changing of pipe size dimensions, restoring the current cal group to the original

factory values. It also allows the user to change flow type from Volumetric, Mass Flow, and Velocity. This block also allows activation and deactiva-

tion of the ST100 FCI TOTALIZER. And finally for the multi-point models of the ST100, this block allows viewing of each individual sensor variables for

the purpose of troubleshooting.