PROFIBUS PA Profile Totalizer Block
This function implements the PROFIBUS PA Profile specified TOTALIZER function. For additional information see the PROFIBUS PA standard.

Totalizer Analog Input Block
This block takes the input data from the Process Data Transducer Block, selected by the “Totalizer Average Channel” and makes it available to other

function blocks at its output.

REL. INDEX

PARAMETER

SLOT

INDEX

DATA TYPE (LENGTH)

STORE

SIZE

READ/WRITE

1

ST_REV

4

17

UNSIGNED16

N

2

R

2

TAG_DESC

4

18

OCTETSTRING

S

32

RW

3

STRATEGY

4

19

UNSIGNED16

S

2

RW

4

ALERT_KEY

4

20

UNSIGNED 8

S

1

RW

5

TARGET_MODE

4

21

UNSIGNED 8

S

1

RW

6

MODE_BLK

4

22

DS-37

S

3

R

7

ALARM_SUM

4

23

DS-42

D

8

R

8

BATCH

4

24

DS-67

S

10

RW

10

TOTAL

4

26

101

N

5

RW*

11

UNIT_TOT

4

27

UNSIGNED16

S

2

R/W

12

CHANNEL

4

28

UNSIGNED16

S

2

R/W

13

SET_TOT

4

29

UNSIGNED 8

N

1

R/W

14

MODE_TOT

4

30

UNSIGNED 8

N

1

R/W

15

FAIL_TOT

4

31

UNSIGNED 8

S

1

R/W

16

PRESET_TOT

4

32

FLOAT

S

4

R/W

17

ALARM_HYS

4

33

FLOAT

S

4

R/W

18

HI_HI_LIM

4

34

FLOAT

S

4

R/W

19

HI_LIM

4

35

FLOAT

S

4

R/W

20

LO_LIM

4

36

FLOAT

S

4

R/W

21

LO_LO_LIM

4

37

FLOAT

S

4

R/W

22

HI_HI_ALM

4

38

DS-39

D

16

R

23

HI_ALM

4

39

DS-39

D

16

R

24

LO_ALM

4

40

DS-39

D

16

R

25

LO_LO_ALM

4

41

DS-39

D

16

R