Topology and Network Configuration
The ST100 supports both Bus topology and Tree topology. Both types have a trunk cable with two terminations. The devices are connected to the

trunk via spurs. The spurs may be integrated in the device giving zero spur length. A spur may connect more than one device, depending on the

length. Active couplers may be used to extend spur lengths.
Active repeaters may be used to extend the trunk length.
The total cable length, including spurs, between any two devices in the Fieldbus should not exceed 1900m. The connection of couplers should be

kept less than 15 per 250m.

Figure 1

Installation

General
For details on the general mounting, placement of sensor head, and mounting options see the Basic User Manual.

Electrical Wiring
Access the wiring terminal block by removing the rear Electrical Connection Cover. This cover can be locked closed by the cover locking screw.

Release the cover locking screw and remove the cover.
Cable access to wiring connections is obtained thru one of the conduit ports.
FCI recommends the use of PROFIBUS PA and FOUNDATION Fieldbus-H1 cable compliant with the “H1 Cable Test Specification FF-844”

The PROFIBUS PA connections for the ST100 are located in

the back panel. The connector pins are labeled “A(+) Pin #2”

and “B(-) Pin #3”. The ST100 PROFIBUS PA connections are

non-polarized, but polarity needs to be observed for other

manufacture’s devices. Connect the Field bus cable as noted

below.
In addition to the PROFIBUS PA connections in the back

panel, the ST100 also has a series of jumpers used to select

other digital communication protocol. Confirm that FF+/PA+

and FF-/PA- have the shorting jumper installed, this select

the output pins for the PROFIBUS PA digital protocol.

PROFIBUS LINE A (+)
PROFIBUS LINE B (-)
PROFIBUS GND

PA+

PA -

JUMPERS SET

C01109-1-1

OUTPUT CUSTOMER CONNECTION

PLC

DISTRIBUTER

TERMINATION

BUS RESISTOR

DP/PA SEGMENT

COUPLER

ST100

ST100

ST100

ST100

ST100

PROFIBUS DP

PROFIBUS PA