5 theory of operation – Hach-Lange RTC113 ST-Module User Manual

Page 13

Advertising
background image

13

General information

Figure 3

Design of the analog and digital input and output modules

Note: The number of LEDs indicates the number of channels.

2.5 Theory of operation

2.5.1

Theory of operation of the RTC Module

The RTC113 RTC Module outputs analog (0/4–20 mA) and digital (0/24 V) signals for the

polymer dosing rate or the feed flow rate of mechanical sludge thickening devices. Digital

fieldbus signals from sc1000 communication cards can also be used.

2.5.2

Input signals

The most important input signals are:

Sludge influent TSS concentration (concentration of solids)

Feed flow rate of the machine-controlled sludge thickening

Thickened sludge TSS concentration (optional)

Status of the thickened sludge pump (on/off)

2.5.3

Parameters for configuration

The most important parameters for configuration are:

The required specific polymer dosing [g polymer/kg TSS]

The target TSS concentration in thickened sludge
Note: In a closed-loop circuit, TSS measurement is required in thickened sludge.

1

Input- or Output- Module or Bus Termination Module

analog or digital

2

LED area with installed LEDs or free LED installation

spaces

2

1

Advertising
This manual is related to the following products: