Parameterization and operation

OUTPUTS

CHANNEL 1

MIN FEED FLOW

Minimum feed flow rate [m³/h] in accordance with 0/4 mA.

m³/h

MAX FEED FLOW

Maximum feed flow rate [m³/h] in accordance with 20 mA.

m³/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set on

connected flow measuring instrument).

MIN POLYMER FLOW

Minimum polymer pump delivery rate in accordance with

0/4 mA.

L/h

MAX POLYMER FLOW

Maximum polymer pump delivery rate in accordance with

20 mA.

L/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set on

connected flow measuring instrument).

CONTROL CYCLE

Pulse/pause mode for the polymer pump open-loop control for

dosing rates beneath the minimum polymer flow rate (MIN

POLYMER FLOW). The on/off duration in pulse/pause mode

can be affected by the duration of the CONTROL CYCLE. For

example, with a CONTROL CYCLE of 100 seconds and a

dosing control value of 60 %, the polymer pump is regularly

switched on for 60 seconds and switched off for 40 seconds.

Short cycle times increase the switching frequency but enable

more precise adaptation to individual requirements. CONTROL

CYCLE should be divisible by MIN RUNTIME and produce a

whole number.

s

MIN RUNTIME

The minimum ON time in pulse/pause dosing mode. The pump

is not activated for periods shorter than this. The MIN RUNTIME

must be shorter than the duration of the CONTROL CYCLE.

s

CHANNEL 2

As per channel one

MODBUS

ADDRESS

Start address of an RTC within the Modbus network. Default

setting: 41–61

DATA ORDER

Specifies the register order within a double word. Presetting:

NORMAL

DATALOG INTRVL

Indicates the interval in which the data is saved in the log file.

[min]

SET DEFAULTS

Restores the factory settings.

MAINTENANCE

RTC DATA

RTC MEASUREMEN

Specifies the value measured by the RTC, e. g. the influent

measurement.

RTC ACTUAT VAR

Specifies the variable calculated by the RTC, e. g. whether the

aeration should be switched on or off.

DIAG/TEST

EEPROM

Hardware test

RTC COMM TO

Communication time-out

RTC CRC

Communication check sum

MODBUS ADDRESS

Here, the address is displayed where the communication

actually takes place. Presetting: 41

4.4.1

RTC113 ST-Module open and closed-loop controller (Continued)

RTC MODULES / PROGNOSYS

RTC MODULES

RTC