Installation – Hach-Lange RTC113 ST-Module User Manual

Page 19

Advertising
background image

19

Installation

8x digital

output

1

KL2408

1

+24 V/0 V

1

Polymer pump on/off (24 V/0 V)

5

+24 V/0 V

1

Closed-loop control of the feed flow rate

active/inactive (24 V/0 V)

2

+24 V/0 V

1

Input signals OK (24 V), input signal faulty (0 V)

6

+24 V/0 V

1

RTC operational (24 V), RTC faulty (0 V)

3

+24 V/0 V

2

Polymer pump on/off (24 V/0 V)

7

+24 V/0 V

2

Closed-loop control of the feed flow rate

active/inactive (24 V/0 V)

4

+24 V/0 V

2

Input signals OK (24 V), input signal faulty (0 V)

8

+24 V/0 V

2

RTC operational (24 V), RTC faulty (0 V)

2x analog

output

KL4012

1(+) - 3(-)

0/4 to 20 mA

1

Output of the polymer pump flow rate

5(+) - 7(-)

0/4 to 20 mA

1

Output of the feed flow rate

2x analog

output

KL4012

1(+) - 3(-)

0/4 to 20 mA

2

Output of the polymer pump flow rate

5(+) - 7(-)

0/4 to 20 mA

2

Output of the feed flow rate

1x analog input KL3011

1(+) - 2(-)

0/4 to 20 mA

1

Input of the feed flow rate

1x analog input KL3011

1(+) - 2(-)

0/4 to 20 mA

1

Input of the polymer flow rate

1x analog input KL3011

1(+) - 2(-)

0/4 to 20 mA

2

Input of the feed flow rate

1x analog input KL3011

1(+) - 2(-)

0/4 to 20 mA

2

Input of the polymer flow rate

Bus termination KL9010

Bus termination

1

Ground to connection 3 and 7 or to the supply voltage connections

Table 4 Connections for the 2-channel RTC113 ST-Module

Module

Name

Connection Signal

Channel Function