5 configuring the switch settings, Onfiguring the, Witch – Cleveland Motion Controls Classic Series DIN Rail Amplifier Non-Isolated MWI-13466 REV CA User Manual

Page 11: Ettings, Ca c

Advertising
background image

MAN-13466

R

EV

CA C

LASSIC

S

ERIES

N

ON

-I

SOLATED

A

MPLIFIER

P

AGE

11

OF

26

Figure 4 - Internal Jumper-switches and Potentiometer Location

2.5 C

ONFIGURING THE

S

WITCH

S

ETTINGS

A number of operational characteristics can be configured prior to mounting or wiring the amplifier. We
recommended that you first familiarize yourself with the internal switch locations, settings, and potentiometers by
opening the snap-on access cover. Figure 4 illustrates the location of configurable items on each of the printed
circuit boards.

Use an approved anti-static wrist strap when adjusting any switch settings/potentiometers on the amplifier.

Switch

PCB Location

Function

J3

Input

Configures Excitation voltage for 5.0 or 10.0 VDC. The amplifier is factory set at (setting 1-2) for
5.0V

J10
J9
J7

Input

Sets voltage gain of the Instrumentation amplifier to 5, 25, 125 or 620. The jumper switches are
factory set to (1-2) for minimum gain (Av = 5). Refer to section 2.8 for more information on setting
Gain select switches.

J1

Output

Configures meter output stage for +/- 2V F.S. or +/- 1 mA F.S. The jumper switch is factory set for
voltage output (1-2). Voltage and current modes use different terminals.

J2

Output

Selects meter damping 0.3 Hz or 3.7 Hz. The jumper switch is set to (2-3) for minimum damping.
(3.7 Hz)


J10

J9 J7

P5
Coarse Zero

Input
Board

Output
Board

J2

J1

J3

I/A Gain

Advertising