2 output wiring, 1 digital voltmeter, Output wiring – Cleveland Motion Controls Classic Series DIN Rail Amplifier Non-Isolated MWI-13466 REV CA User Manual

Page 15: Ca c

Advertising
background image

MAN-13466

R

EV

CA C

LASSIC

S

ERIES

N

ON

-I

SOLATED

A

MPLIFIER

P

AGE

15

OF

26

2.12.2 O

UTPUT WIRING

The load in this connection may be an indicator, recorder, data acquisition device or the analog input terminals of a
control device such as a DC drive or a programmable logic controller. The output signal at this terminal is
undamped and is the output terminal that provides that fastest response to changes in the transducer (load-cell) load.
Note that the cable’s shield drain wire should be connected at only one end, preferably at the “receiving end”.

8

7

1

2

3

5
6

4

2

1

6

4
3

5

7

8

SHIELD GND

RESISTANCE

5000 OHM MIN

+ / - 10V LOAD

+

Figure 7 - Output Wiring, +/- 10V Analog

2.12.2.1 D

IGITAL

V

OLTMETER


The +/- output terminal is designed to provide +2.0 volts when the +/- 10 V output terminal is adjusted (with the
Gain and Zero pots) to be +10.0 volts (this is full scale). To achieve different scaling, adjust gains on the Digital
Panel meter (DPM).

DIGITAL VOLT METER

+

7
8

2
1

3
4

6

5

1
2

8
7

5

3

4

6

0 TO 1.99 VOLT

MINIMUM METER RESISTANCE = 2000 OHMS

Figure 8 -

Output Wiring, Damped +/- 2V Analog