Maintenance and Adjustments

6

CAUTION

Door closing force is FACTORY set and requires no adjustment
for normal operation.

NEVER adjust the force settings to compensate for damage,

including an unbalanced door, binding door track, or broken
spring.
• Perform monthly a CONTACT REVERSE TEST. See page 8.

ADjUSTMENT GUIDES

Force Settings
Force settings are pre programmed at the factory and “learned”
during the Open/Close Limit settings steps (see pages 6-7). For normal

use, these settings should not need adjustment with this unit.

However, conditions possibly requiring adjustment are:
1. Doors with very stiff weather seals.
2. Doors that start down, STOP, and reverse before closing.
3. Doors that start up, but STOP before they completely open.

Force Adjustment

(continued next page)

Force Level

Powerhead LEDs

ROUND LED

LONG LED

LED indicator colors:

OFF

Blue

Purple

Red

Force Level 1

BLUE

BLUE
BLUE

BLUE

Off

Off

Off

Off

Force Level 3

Force Level 4

PURPLE

PURPLE
PURPLE

PURPLE

Off

Force Level 6

Force Level 7

RED

RED

RED
RED

Off

Force Level 9

Force Level 2

Force Level 5

Force Level 7

PROGRAM

SET

PROGRAM

SET

The Current

UP FORCE SETTING

will display. SEE CHART IN NEXT
COLUMN.

Action

LED Indication/Result

Press and hold

both up and

down buttons

2 seconds or until round

LED turns RED.

Press either

until you reach

desired setting.

Press and

release.

Press either

until you

reach the

desired setting.

Press and

release.

USE CHART IN NEXT COLUMN

USE CHART IN
NEXT COLUMN

LOCKS IN SETTING.
Then the New
DOWN FORCE
SETTING will display.

OFF

RED

OFF

BLUE

Flashes 3 Times

BLUE

Flashing

OFF

BLUE

BLUE

LOCKS IN SETTING.
Both LEDs turn
BLUE then OFF
confirms both
FORCE Settings are reset.

BLUE

BLUE

OFF

OFF

FORCE SETTINGS DONE

1

2

3

4

5

18

G999-393 Manual-ScrewBeltChain-EN indd 18

7/13/12 10 17 AM