Input channel configuration, Analog input readings – Impulse MAQ20-940 Configuration User Manual

Page 12

Advertising
background image

MAQ

®

20 Configuration Software Tool User Manual

6

4.0

Configuring the MAQ

®

20 Volt/Millivolt Input Modules

Figure 6: MAQ20-VDN Voltage Input Module Configuration Panel


To configure the module click on any cell in a row of the Main Registration Panel and then click the
Configure Module button this will open the MAQ20 volt input configuration panel. The three types of
Voltage Input Modules are 8-channel differential voltage input, 8-channel differential Millivolt input and 16-
channel single ended voltage input. Selectable on a channel-by-channel basis, the input ranges for the
Voltage input models are ±60V, ±40V, ±20V, ±10V and ±5V and the input ranges for the Millivolt model
are ±2V, ±1V, ±0.25V, ±0.1V and ±0.05V.

4.1

Input Channel Configuration:

Input Range settings can be set on a channel-by-channel basis along with the Avg Weight used for the
average value calculation. The average calculation uses 2^(Avg Weight) samples, i.e. the average
calculation for the configuration shown above uses the most recent 2^(3) = 8 samples. If changes are
made to the Range or the Avg Weight, the appropriate Set button must be pressed to write the settings to
the module nonvolatile memory. A Scan List is provided to give the ability to scan between 1 and n
sequential channels, where n = 8 for 8-channel modules and n = 16 for 16-channel modules. A Scan List
value of n specifies that channels 0 through n-1 will be sampled. The default scan list setting is 8 for
differential modules and 16 for single ended modules. Pressing the Set button sends the data to the
input module and the scan list will remain active until the next power cycle. Press the Save button to
store the settings to the module nonvolatile memory.

4.2

Analog Input Readings:

Data read from each of the active channels is displayed in this section. Data can be displayed in Counts
or Engineering Units (Volts). If the Loop Read check box is selected data will update every 0.5 second
and if it is unselected, data is manually updated by pressing the Read button. The Read Type drop down
box gives the user the ability to select what type of readings will be displayed (Current, Average,
Maximum or Minimum). The Alarm Status colors are used when channels are configured with alarm