limits. When an alarm limit for a given channel is exceeded, the background color of the cell displaying
data for that channel will change indicate which limit has been exceeded.

4.3

Alarm Configuration for Input Channels:

This section is used to configure alarm settings for each channel. Alarm choices are High, Low, High-
High and Low-Low. High / Low and High-High / Low-Low ranges have separate Dead Bands which can
be specified. Alarm limits must have the same units as the Analog Input Readings (Counts or
Engineering Units). Enter the alarm limits and press the Set Alarm Settings button to write the values to
the module. Press the Save button to store the settings to the module nonvolatile memory.

4.4

Reset Input Readings:

These buttons clear the registers used to store the Maximum, Minimum and Average values of data read
from each channel.