3 – units of measure – Liquid Controls Sponsler T675 - Cryogenic System Register User Manual

Page 17

Advertising
background image

Sponsler, Inc.

Model T675 Flow Totalizer

Technical Information

Pg. 14

Enter setting (ESC to exit)?


Product temperature ranges:

Temperature

Low

Reference:

High

Product

°K

°C

°F

°K

°C

°F

°K

°C

°F

LOX

88.0

−185.15

−301.27

90.180

−182.970 −297.346

110.0

−163.15

−261.67

LIN

75.0

−198.15

−324.67

77.364

−195.786 −320.411

95.0

−178.15

−288.67

LAR

85.0

−188.15

−306.67

87.284

−185.866 −302.555

107.0

−166.15

−267.07

LCO2

233.1

−40.05

−40.09

256.762

−16.388

2.502

266.2

−6.93

19.53

LN2O

222.1

−51.09

−59.96

238.470

−34.680

−30.424

288.5

15.38

59.69

CCO2

233.1

−40.05

−40.09

247.317

−25.833

−14.499

266.2

−6.93

19.53

MAPP

255.3

−17.87

−0.17

288.534

15.384

59.691

324.1

50.92

123.66

LPG

233.1

−40.05

−40.09

288.534

15.384

59.691

323.1

49.94

121.89

3.2.2.3 – Units of measure
Allows selecting the unit of measure, commonly referred to as Engineering Units, for the Ratemeter, Totalizer, and
Temperature displays. All displays are independent. Depress the corresponding number in the left column to
select the display to be programmed, entry is automatic.

Example: Select Totalizer; <2>

************ Unit of measure ***********

1 – Ratemeter
2 – Totalizer
3 - Temperature

Enter setting (ESC to exit)?


Depress the corresponding Engineering Unit of measure number in the left column, entry is automatic.

Example: Select Liters for the Totalizer; <2>

Display for Unit of measure Options 1 and 2

*************** Ratemeter **************
*************** Totalizer **************

Current setting = 1


1 – Gal
2 – Litre
3 – Lbs
4 – Lbs x 10
5 – kg
6 – Scf
7 – Scf x 100
8 – m3

Enter setting (ESC to exit)?