Hrv p700sdd – American Aldes HRV 700SDD User Manual

Page 4

Advertising
background image

PRODUCT

SPECIFICATIONS

AND ENGINEERING

INFORMATION

-----

SUBMITTAL DATA

497HRV70-4-03

GENERAL FEATURES

Thermally conductive aluminum heat exchange core, cross-
flow design, easily removed for cleaning or service.

Insulated 20 gauge white powder coated galvanized steel
cabinet.

Direct drive centrifugal forward curve blowers, Multi-speed
providing 400 to 650 cfm. one in each air stream.

Two efficient three speed PSC double shafted motors 120 V,
2.75 Amps each (5.5 Amps total on high speed),
1 ph. 1/10 HP, 1625 RPM. Watts - total on high speed - 648

Washable filters, one in each air stream protect the core. Easy
to access and clean.

Installation accessories and controls make installation simple.

ALDES Pool Model Heat Re-
cover Ventilators are designed
to exhaust humid air from indoor
swimming pools and spa area
and to supply tempered fresh air
from outdoors. It incorporates
an efficient aluminum core for
heat recovery of waste heat to
temper the fresh outdoor air, to
provide and economical solu-
tion to excessive humidity, odor,
stuffiness, and other indoor air
pollutants. The model P700SDD
is intended for small commer-
cial, institutional, and residential
applications for pool and wetted
deck areas up to 700 square
feet.

The pool model has three modes
of operation to meet the unique
needs of pools. The normal
ventilation mode provides ex-
haust of humid air and supply of
fresh outdoor air, with heat re-
covery in the efficient aluminum
cores. This mode is controlled
by an adjustable dehumidistat
that opens the fresh air damper
to the outdoor air intake, and
operates both the supply and
exhaust fans. (A duct heater or
hot water coil may be installed in
the supply duct to provide addi-
tional heat to the incoming air or
recirculating air. This heater
would be controlled by a duct
mounted thermostat.)

The second mode of operation
occurs when the humidity level
falls below the setpoint of the
dehumidistat. The exhaust fan
shuts off, the supply air damper
closes off outdoor air, and opens

The third mode of operation pro-
vides automatic defrost by shut-
ting off fresh air intake in a cycle
of 4.5 minutes off, 17 minutes
on. The defrost cycle occurs
when outdoor temperatures are
below 27°F (-3°C)

the recirculation air circuit. This
mode maintains constant air cir-
culation in the conditioned space,
and a means of heating the con-
ditioned space if a duct heater or
hot water coil is installed in the
supply duct.

HRV P700SDD

HEAT RECOVERY VENTILATOR

POOL MODEL

ALDES HRV P700SDD

Heat Recovery Ventilator

for Swimming Pools

PART NO. 28 110

Standard Damper

Defrost