Target superheat testing, Temperature split testing, Actual superheat testing – Mastercool 52251 A_C SYSTEM ANALYZER User Manual

Page 3

Advertising
background image

3

www.mastercool.com

• Use ► or ◄ buttons to highlight digit and ▲ or ▼ buttons

to change digit value.
• Press

ENTER to toggle between Height and Width.

NOTE: Be sure to press ENTER for both Height and Width

before pressing done.
• Press

F1 when DONE entering duct size.

• Place round vane meter or antenna fan meter

perpendicular to air flow to read volume.

TARGET SUPERHEAT TESTING

• Target Superheat Testing uses the round vane meter or

antenna fan meter. For round vane meter, twist sensor

cover to the Open position. For antenna fan meter, go to

next step.
• Insert cable into socket (it may take a few seconds for

readings to appear).
• Follow Target Superheat 1 screen instructions on where to

place round vane meter or antenna fan meter.
• When values have stabilized, press

ENTER to save.

• Press

F2 (NEXT).

• Follow Target Superheat 2 screen instructions on where to

place round vane meter or antenna fan meter.
• When values have stabilized, press

ENTER to save.

• Press

F2 (NEXT).

• Target Superheat will be displayed on the screen.
• If Actual Superheat has been tested, Press

F1 (ANYL) for

analysis.

TEMPERATURE SPLIT TESTING

• Temperature (TEMP) Split Testing uses the round vane

meter or antenna fan meter. For round vane meter, twist

sensor cover to the Open position. For antenna fan meter,

go to next step.

• Insert cable into socket (it may take a few seconds for

readings to appear).

• Follow Temp Split 1 screen instructions on where to place

round vane meter or antenna fan meter.

• When values have stabilized, press

ENTER to save.

• Press

F2 (NEXT).

• Follow Temp Split 2 screen instructions on where to place

round vane meter or antenna fan meter.

• When values have stabilized, press

ENTER to save.

• Press

F2 (ANYL).

• Target Temperature Split and Actual Temperature Split with

analysis will be displayed on the screen.

ACTUAL SUPERHEAT TESTING

• Use ▲ or ▼ buttons to highlight Actual Superheat.

• Press ENTER.
To Input Pressure Manually
• Use ▲ or ▼ buttons and highlight Input Manually.
• Press

ENTER.

• Use ▲ or ▼ buttons to highlight refrigerant.
• Press

ENTER.

• Use ► and ◄, buttons to highlight unit and ▲ and ▼

buttons to adjust unit value to input low-side saturated

pressure.
• Press

ENTER.

• Saturated vapor temperature will be displayed.