Calibration – Mastercool 52251 A_C SYSTEM ANALYZER User Manual

Page 6

Advertising
background image

6

www.mastercool.com

NOTE: The Customer or Test can be deleted by pressing F2

(DEL) when they are highlighted.

CALIBRATION

• Use

POWER button to turn on A/C Analyzer.

• From MAIN MENU press

CAL button.

For Thermocouple Calibration
NOTE:
Press F4 (EXIT) in Thermocouple Cal 1 Screen to

return to MAIN MENU without saving, or

F2 (PT) to calibrate

the pressure transducer.
• Insert thermocouple into thermocouple socket.
• Place thermocouple at known temperature and allow

temperature to stabilize.
NOTE: Use crushed ice and just enough water to cover and

calibrate to 32˚F or 0˚C, or place thermocouple clamp on a

heavy wall copper pipe and clamp a calibrated meter next to

it.
• Use ► and ◄, buttons to highlight unit and ▲ and ▼

buttons to adjust unit value to input calibration temperature.
• Press

F1 (CAL) button.

• If thermocouple has correct reading, press

F4 (EXIT) to

save.
• If thermocouple reading is off, Press

F1 (REDO) to redo the

calibration.
For Pressure Transducer Calibration
CAUTION:
To calibrate the pressure transducer you will

need a source of high-pressure gas with a highly accurate

calibrated gauge. Do not start calibrating the pressure

transducer without it. For best results, calibrate sensor at

close to its maximum value.
NOTE: Press F4 (EXIT) in Pressure Transducer 1 and

Pressure Transducer 2 Screens to return to MAIN MENU

without saving, or

F2 (TC) to calibrate the thermocouple.

• If in Thermocouple 1 screen, Press

F2 (PT) button to

display Pressure Transducer 1 screen.
• Two pressures are required, one low and one high.

Atmospheric (0) is OK for the low pressure.
• With the pressure transducer at low pressure, use ► or ◄,

buttons to highlight unit and ▲ or ▼ buttons to adjust unit

value to input the low pressure.
• Press

F1 (NEXT).

• With the pressure transducer at the high pressure, use ►

or ◄, buttons to highlight unit and ▲ or ▼ buttons to adjust

unit value to input the high pressure.
• Press

F1 (CAL).

• If pressure transducer reading is correct, Press

F4 (EXIT)

to save and return to MAIN MENU.
• If pressure transducer reading is off, press

F1 (REDO) to

redo the high pressure setting.

SPECIFICATIONS:

System Analyzer

• Operating Temperature: 0 to 50˚C (32 to 122˚F), humidity <80%

• Storage Temperature: -20 to 50˚C (-4 to 122˚F), humidity <90%

• Dimensions with boot: 191mm x 93mm x 41mm

• Weight: (meter w/ batteries & round vane) 500g

• Temperature Display: ˚F and ˚C

• Pressure Display: PSI and Bar

• Backlit LCD Display

• Low battery indicator
• K-type thermocouple connection