120411 - V2

Power Rating

Output Power rating (KVA)

10

20

30

40

50

80

100

120

150

Output Power Rating (KW) - 0.80 PF

8

16

24

32

40

64

80

96

120

Energy Usage

Efficiency at 50% Load

89.5%

88.7%

90.5%

90.5%

92.2%

92.5%

92.9%

93.1%

93.3%

Efficiency at 100% Load

90.0%

89.0%

91.0%

91.0%

91.8%

92.0%

92.4%

92.7%

92.8%

BTU/hr at 100% Load

3,036

6,751

8,104

10,808

12,201

19,005

22,472

25,819

11,795

Physicals

Dimensions, w x dp x h (in.)

27 x 32 x 71

27 x 32 x 71

27 x 32 x 71

Weight, module only (lbs)

735

763

970

1,147

1,257

1,489

1,929

2,006

2,160

Input

Voltage

480/277V 3ph 3w or 4w + gnd ; Input Source must be 480/277V grounded wye

Topology

6-Step Thyristor Bridge Rectifier

Input Filter

5th Harm

Dual Input Capable

Remove internal jumper cables for separate inputs to Rectifier & Static Bypass

Voltage Range (w/o battery discharge)

-20% to +15%

Power Factor (lagging)

0.93 (w/input filter); 0.80 w/o input filter

Current THD

< 10% (w/input filter)

< 7% (w/input filter)

Frequency

60Hz +/- 10%

Output

Voltage

480/277V 3ph 3w or 4w + grd

Topology

PWM IGBT Inverter w/SVM Technology and ZigZag Isolation Transformer

Frequency

60Hz +/- 10%

Crest Factor

3 : 1

Static Voltage Regulation

+/- 1%

100% Step Load Voltage Regulation

+/- 3%

100% Linear Load Voltage Distortion

2% THD maximum

100% Non-Linear Load Voltage Distortion

3% THD maximum

Overload Capability/Inverter

125% for 10 min ; 150% for 1 min

Overload Capability/Static Bypass

110% continuous ; 200% for 5 minutes

Battery Plant

Compatible Technologies

VRLA, Premium Durathon VRLA, Wet Cell (and DC Flwheel technologies)

Float Voltage

545 VDC @68 degr F (20° C)

Recharge Time

10X discharge time (at 30min battery runtime)

Internal Batteries Available

Yes

No

General

Audible Noise

60 db(A)

63 db(A)

65 db(A)

Ambient Operating Temp

UPS Module: 32 to 104 degr F (0-40° C)

Humidity

0-95% non-condensing

Certifications

Seismic Certified , GE EcoMagination Certified

Listings/Registrations

UL1778 / IEC62040 / ISO 9001

Enclosure

IP20 and NEMA PE-1

RFI/Surge Protection

EN50091-2 / IEC 62040-2 / IEEE 587B / FCC Class A Part B Compliance. Special FCC Filters available

Communication/Connectivity

RS232, programmable alrms contacts, programmable relays, optional SNMP, Modbus

Color

Black w/grey logo & kickplates

Warranty

12 month after startup or 18 month after shipment (whichever first). Extended warranties available.

Technical Specifications

For more technical information, please refer to applicable product Technical Datasheet

Advertising