When connecting the 4150 / 4150X to a loop with a resistive load greater than 250 Ωs, the HART jacks may
be connected across the loop + and – or to the HART device communication terminals. Refer to the
following diagram for connecting across the loop + and -.



HART

®

Communications

Initial Screens / Online Mode
Upon power up the 4150 / 4150X automatically detects if a field device is connected and attempts to
establish HART communications; this is the factory default “Auto” poll function. When a device with
address zero is found, the 4150 / 4150X provides feedback to the user and starts the initial HART display for
the connected device. See an example of Online Mode below.








Online

#

3051 : PT-1012D
1 Device setup
2 Pres: 0.01 inH2O
3 AO: 4.001 mA
4 LRV: 0.00 inH2O
5 URV: 250.00 inH2O



Up Down Select Back

Connecting to communication terminals

Initial HART Screen / Online Mode

Main Navigation Screen

Auto Poll Launch; Device “0” found

Communicator

#

1 Online Setup
2 Offline Menu


Device 0: *On-Line*
Rosemount
3051C
Fld Dev Rev 03
Dof Name 26060309
Up Down Select Cfg