G15 auto/manual switch - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 45

Advertising
background image

G15
AUTO/MANUAL SWITCH - 3

INPUTS

NAME

SYMBOL

DATAPOINT

CONTROL OUTPUT

CO3

C231

AUTO ENABLE

AE3

L186

OUTPUT TRACK VALVE

OTV3

C237

OUTPUT TRACK SWITCH

SWOTV3

L189

PARAMETERS

OUTPUT TRACK ENABLE

OTE3

L191

HARD MANUAL LIMIT

HML3

L194

OUTPUT HIGH LIMIT

OH3

C217

OUTPUT LOW LIMIT

OL3

C218

OUTPUT SLEW RATE

T33

C226

OUTPUTS

OUTPUT

OUT3

C210

OUTPUT TRACK STATUS

OVTS3

L177

AUTO STATUS

AUT3

L179

Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.