F-cim 51 pid - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 64

Advertising
background image

F-CIM 51
PID - 1

NOT REUSABLE

NAME

SYMBOL

DATAPOINT

INPUTS

S

n-1

DEVIATION

DV1

C157

A

[unused]

B

RESET FEEDBACK

RF1

C163

C

CONTROL TRACK COM-
MAND

CTC1

L147

PARAMETERS

PROPORTIONAL BAND

PB1

C142

RESET TIME

TR1

C143

RATE TIME

TD1

C144

OUTPUT HIGH LIMIT

OH1

C145

OUTPUT LOW LIMIT

OL1

C146

MANUAL RESET

MR0

C147

INSTRUMENT RANGE

IR1

C151

FEED FORWARD

FF1

C158

REVERSE SWITCH

RSW1

L130

OUTPUTS

S

n

CONTROL OUTPUT

CO1

C159

Description:
This module computes a control output signal based on the above listed inputs and parameters.
The result is simultaneously available as the module output Sn and as a database parameter CO.
The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the control track command
input is less than one, the module output will track the reset feedback input (B) by back calculating
the integrator term. When (C) input is greater than or equal to 1 the reset feedback is used by the
integrator to calculate the next output and should reflect the value (scaled 0-100%) of the value of
the final control element. For standard PID controller reset feedback, (B) should be OUT and con-
trol track command should be AUT.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

3-12

Advertising