F-CIM 57
DEVIATION/ALARM CALCULATION - 1

NOT REUSABLE

INPUTS

NAME

SYMBOL

DATAPOINT

S

n-1

SETPOINT

SP1

C137

A

PROCESS VARIABLE

PV1

C136

PARAMETERS

SETPOINT SLEW RATE

T11

C153

CONTROL ZONE

C21

C150

ALARM INDEX

AIX1

B340

ALARM LIMIT 1

PL11

C139

ALARM LIMIT 2

PL21

C140

ALARM DEADBAND

ADB1

C141

OUTPUTS

S

n

DEVIATION

DV1

C157

ALARM A

PA11

L134

ALARM B

PA21

L135

TRUE SETPOINT

TSP1

C155

Description:
This module calculates and loads the deviation value based on setpoint (S

n

) and

process variable (A). Before the calculation is performed the setpoint value is con-
ditioned so as not to exceed the rate of change limit specified by T1. If the calcu-
lated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and
ADB. Results of the alarm tests are loaded to PA1 and PA2. Refer to Section
4.1.6 of Instruction Bulletin 53MC5000 for an explanation of AIX values.

MODULAR CONTROLLER CUSTOMIZATION GUIDE