Micromod MOD: 30ML Installation User Manual

Page 19

Advertising
background image

MOD 30ML Multiloop Controller

PRODUCT DESCRIPTION

1.4.3 2012A Current Input Module (with 2-wire transmitter power)

This module is designed specifically for two-wire transmitters and provides the necessary 24
V DC current limited supply to power the transmitter. An internal current sense resistor
converts the current to a voltage for application to the A/D converter. All other features are
the same as the voltage input module. This module uses the Voltage/Current Input Module
(VCIM) Block for configuration of input parameters.

VCIM

Catalog Number Description for 2012A

BASE NUMBER

2012A

Current Input Module (with 2-wire transmitter power)


UNUSED

Z

Unused Character


ELECTRICAL CODE 10

General Purpose


INPUT RANGE

10

4 – 20 mA

ISOLATION

1

Isolated


MODEL

B

Design Level


Sample Number

2012AZ10101B


1.4.4 2013A Thermocouple Input Module (with upscale burnout detection)

The thermocouple input module is identical to the ±100 mV voltage input module except for
the addition of upscale burnout detection circuitry. Thermocouple types allowed are: B, E, J,
K, N, S, or T. This module uses the Thermocouple Input Module (TIM) Block for
configuration of input parameters.

Cold junction compensation (CJC) for all thermocouples is provided automatically by the
controller when this feature is enabled by connection of a thermocouple to built-in input 1. If
automatic CJC is not enabled, a 2009A RTD Input Module with a 2-wire CJC sensor must be
used to sense the temperature at the terminal block and provide CJC.

TIM

Catalog Number Description for 2013A
BASE NUMBER

2013A

Thermocouple Input Module

(with upscale burnout detection)


UNUSED

Z

Unused Character


ELECTRICAL CODE 10

General Purpose


INPUT RANGE

10

±100 mV

ISOLATION

1

Isolated


MODEL

B

Design Level


Sample Number

2013AZ10101B

13

Advertising