5 2011a form c mechanical relay outputs (wdom) – Micromod MOD: 30ML Installation User Manual

Page 78

Advertising
background image

MOD 30ML Multiloop Controller

MODULAR I/O CONNECTIONS

4.4.5 2011A Form C Mechanical Relay Outputs (WDOM)

Make mechanical relay output connections as shown in Figure 4-15.
Wire rating: 600 V, -20°C +105°C UL, CSA approved. Output specifications are:

FORM C MECHANICAL RELAY OUTPUT

Configuration

Form C single relay

Power supply range

+ 5 VDC ±10%

Max Input Current

-10.0 mA DC

Contact load

3A at 60 VAC or 30 VDC

Contact resistance

0.10 ohms maximum

Isolation

250 Vrms (contacts to coil)

Current rating

3A per relay

Response time

10 msec


72