Output Holder Instructions

CONFIGURATION

Figure 4 .6. Execution Order



If you are using the MOD30 Conversion Style Instrument, change Input Signal Range
of PV to 1 to 5 Volts and RETURN to 0.25 to 1.25 Volts.

8. Optionally you can include the output holder feedback (RETURN) only in the

configuration and not the presence of the output holder (SENSE). In this case you do not
need the discrete input module in the controller. The configuration will not have the
SENSE (DIM), SENSEF (DI) and the OP_T_LGC (EX) blocks. You can delete these
blocks from the loaded compound. You would still need to connect a track command
input to the PID block. This will again be the RUNINIT signal from the IF block connected
to the TCI attribute of the PID block ensuring bumpless transfer of the output value. Refer
to the section 4.4 Connection RUNINIT from the IF block, Option 2 for the procedure.


9. Compile and download your database to the controller.