Appendix B: Summary of Error Messages

E1

MIN

INT

is caused by a Low-Level fault with a Low-Level

Switch connected to the pump. The pump is stopped

and the alarm outputs are activated. This operates in all

Internal and External modes. The pump automatically

restarts when the fault is cleared.

E2

FLOW

INT

indicates that the pump has lost prime. Again, the pump

is stopped and output alarms activated. Item 4 in the

Advanced Menu must be disabled (set to 0), it is not

usable with the HH9 pump.

E3

MIN

EXT

:

is displayed in the External mode if the stroke rate

exceeds 100 SPM. The pump is NOT stopped and NO

alarm outputs are activated with this fault. To stop E3

flashing, clear the fault condition, then stop and restart

the pump.

E4

EXT

X

is displayed in the External X (Batch) mode in two

situations. 1) If "Batch Accumulate" is disabled and a

pulse signal is received while the pump is counting

down. The pump is not stopped, and the alarms are not

activated. To clear the E4 message, the pump must be

stopped and restarted. 2) If "Batch Accumulate" is

enabled and the cumulative batch value exceeds 999, E4

will be displayed. The E4 message can only be cleared

if the pump is stopped and restarted.

E5

FLOW P12

EXT

is displayed in the mA External mode if the mA input

value exceeds 21.0 mA, whether the pump is running or

stopped. Again, the alarms are NOT activated. Once

the mA signal goes below 21.0 mA, the E5 error

message is cleared.

(HH9 Only)