3 transducer block, 1 transducer block parameters, 2 password parameters – Orion Instruments Jupiter 2xx FOUNDATION Fieldbus User Manual

Page 16

Advertising
background image

16

57-649 Jupiter Magnetostrictive Transmitter - F

OUNDATION

fieldbus™

3.3

Transducer Block

The TRANSDUCER block is a custom block containing
parameters that support the enhanced level transmitter. It
contains the Jupiter probe configuration, diagnostics, and
calibration data, and outputs level with status information.

The TRANSDUCER block parameters are grouped in a
useful configuration. There are both read-only parameters
and read-write parameters within the TRANSDUCER block.

• The read-only parameters report the block status and

operation modes.

• The read-write parameters affect the function block basic

operation, level transmitter operation, and calibration.

The Transducer Block Mode will automatically be changed
to “Out of Service” when the local interface (keypad) is
used to change a parameter online.

3.3.1 Transducer Block Parameters

The first six parameters in the TRANSDUCER block are
the universal parameters discussed in section 3.1.1. The
universal parameters are followed by these additional
required parameters:

UPDATE_EVT (Update Event): an alert generated by a
write to the static data in the TRANSDUCER block.

Another important parameter found later in the TRANS-
DUCER block list is DEVICE_STATUS, which displays
the status of the device. If more than one message exists,
then the messages are displayed in priority order. Refer to
Section 5.1.2, Status Messages.

If DEVICE_STATUS indicates a problem, refer to
Section 5.1.1, Troubleshooting (those parameters which are
shaded are password-protected).

For a complete list of Transducer Block Parameters, refer
to table in the Appendix.

3.3.2 Password Parameters

To change a parameter at the local user interface, a value
matching the user password must be entered (Default=1). If
the user password is entered, the instrument is in the user
mode. After 5 minutes with no keypad activity, the entered
password expires.

Factory password is for use by trained factory personnel only.

From the network, the instrument always behaves as if it is
in the user mode by default. In other words, it is not neces-
sary to enter the user password in order to write parameters
from the network.

Advertising