Hardware

7

Overview for Avaya IP600 Internet Protocol Communications Server
555-233-001 — Issue 5 — November 2000

1

The Avaya IP600 should be installed in a well-ventilated area. Maximum equipment
performance is achieved at an ambient temperature between 40 and 120 °F (4 and
49 °C) for a short-term operation (not more than 72 consecutive hours or 15 days in a
year) and up to 110 °F (43 °C) for a continuous operation.

The relative humidity range is 10% to 95% at up to 84 °F (29 °C). Above this,
maximum relative humidity decreases from 95% down to 32% at 120 °F (49 °C).
Installations outside these limits may reduce system life or affect operation. The
recommended temperature and humidity range is 65 to 85 °F (18 to 29 °C) at 20% to
60% relative humidity.

The other Environmental Considerations and System Protection requirements
described in the DEFINITY ECS Systems Description under “Site Requirements”
apply to the Avaya IP600 as well.

Table 1.

Cabinet Power Source Information

Cabinet Style and Power

1

Distribution Unit

Power Sources

Power Input Receptacles

Rack Mount Cabinet. AC power
supply

(650A integrated power

supply)

Single phase 120 VAC with neutral

Single phase 240 VAC with neutral

120 VAC, 60 Hz NEMA 5-15R

240 VAC, 50 Hz IEC 320

Japan installations use country
specific receptacles for 100 and
200 VAC, 50/60 Hz

1

There is no integrated DC power supply. DC rectifiers can be used if desired; follow manufacturer’s instructions.

Table 2.

Circuit Breakers for AC-Powered Cabinets

Cabinet Type

Circuit Breaker Size

Rack Mount Cabinet (120 VAC) 60 Hz

15 A

Rack Mount Cabinet (240 VAC) 50 Hz

10 A