Electric IOM

14

Electrical Requirements

1. Connect wiring as shown in the specific

wiring diagram which is furnished inside
the cover of the electrical control box. Be
sure to install a separate fused
disconnect for the boiler. All wiring must
conform to NEC Code.

WARNING

Prior to powering up the boiler, all electrical
contacts require re-torquing to the
individual compenents manufacturers
recommendations.

2. A correctly sized fused disconnect switch

should be fitted as close to the boiler as
possible and connections made to the
boiler control panel in compliance with
NFPA (National Fire Protection
Association), NEC Code, and local
codes. The appropriate number of
terminals are provided inside the control
panel box to take these connections, but
the panel box must be drilled to accept

the type of conduit used.

6HHDGGLWLRQDO

Boiler Controls

Fulton packaged electric steam boilers are
equipped with both a steam pressure
control and a high limit pressure control
mounted on the outside or inside of the
electrical panel box.

1. The steam pressure control should be

adjusted to suit the boiler application.
The control has two scales (main and
differential) which can be adjusted by
means of screws on top of the control.
The main scale setting should be
adjusted to the desired operating steam
pressure.

CAUTION

Do not adjust to exceed the pressure
rating on the boiler.

2. A high limit pressure control is located

next to the operating steam pressure

control and should be set 5 to 10 pounds
higher than the operating steam
pressure control. This control serves as
a secondary high pressure cut-off if for
some reason the main operating steam
pressure control should become
inoperative.

Low Water Control
Relays

1. Boilers from 1.2 to 3.6 HP are e quipped

with one low water cut off relay in the
panel box connected to two
independent probes in the top of the
boiler and one water level control relay
in the panel box operating two probes in
the top of the boiler.

2. Boilers from 5 - 20 HP contain two low

water cut off relays in the panel box
connected to two independent probes in
the top of the boiler.

3. Boilers from 30 - 100 HP have an

external water column on the right hand
side of the boiler. There are two low
water cut off control relays in the panel
box. One connects to a probe in the top
of the boiler and the other connects to a
probe in the top of the water bottle.

Installation

Electrical Power Requirements (In Amps)

Model FB-L

012

015

018 024 030 036

050

075

100

150

200

300 500

750

1000

208V 3 Phase

34

42

50

67

84

100

139

208

278

416

556

832

--

--

--

230V 1 Phase

52

65

78

--

--

--

--

--

--

--

--

--

--

--

--

230V 3 Phase

29

36

43

58

73

87

120

180

241

361

482

724

--

--

--

460V 3Phase

15

18

21

29

36

44

60

90

120

180

241

363 607

906

1204

575V 3 Phase

13

16

18

24

30

36

50

76

101

150

201

301 502

756

1004