Maintenance, Recommended quarterly maintenance, Recommended six month maintenance – Fulton Electric (FB-L) Steam Boiler User Manual

Page 29

Advertising
background image

CAUTION

Do not clean the gauge or gauge glass
while pressurized or in operation.

a) Clean the water gauge glass using a

commercial non-abrasive glass
cleaner. Use diluted acids such as
hydrochloric (muriatic) acid when
regular cleaners do not seem to work.
Do not use wire brushes or any other
abrasive materials which could
scratch the glass. If any leakage is
evident, replace the gaskets.

b) Always replace the high impact plastic

gauge glass protector which is
standard on all Fulton Boilers.

6. Clean water pump strainers.

7. Check operation of all steam traps on

condensate return system.

8. Remove pipe cap at the cross connection

below water column and clean nipple
into boiler. Boiler must be cold and
water level below pipe, (30 - 100 BHP
only).

Recommended Quarterly
Maintenance

1. Shut off the boiler completely and drain.

2. Remove the handholes and inspect the

interior of the vessel for scale or sludge
deposits. The amount of deposits will
indicate the efficiency of the water
treatment being used. The frequency of
this inspection will be dependent on the
condition of the water side of the boiler.

3. Replace handhole gaskets using the

following procedure.

a) Remove old gasket and thoroughly

clean the surface on the boiler and
the plate.

b) Place gasket on handhole plate. Be

sure the gasket is pushed down tight
on the plate. Do not use any grease,
lubricant or adhesive.

c) After the plate is in the boiler and the

gasket is in place, set yoke and
tighten nut only enough to provide a
snug fit. Make it hand tight and then
snug with wrench about 1/4 turn. Do
not compress excessively.

d) If the gasket leaks while pressure is

being built up, tighten only enough to
stop leakage. Never tighten more
than necessary to prevent leakage.
Excessive tightening may shorten life
of the gasket.

4. Refill the boiler with fresh water.

Recommended Six
Month Maintenance

1. Steam Safety Valve - Under normal

operating conditions a “try lever” test
should be performed approximately
every six months. Testing should be
performed more often under severe

service conditions or if corrosion or
deposits are noticed within the valve
body. A “try lever” test should also be
performed at the end of any extended
non-service period. Check that the
steam safety valve is operating properly
by conducting a “try lever” test.

CAUTION

Prior to performing the “try lever” test,
be certain to take precautions as a loud
noise and high velocity steam will
discharge freely from discharge port
and through drain hole provided in the
side of the valve body.

a) The test lever is designed to be

activated only when 75% or more of the
relief pressure is reached, otherwise
distortion could result. The valve
should be tested at or near maximum
operating pressure by holding the test
lever fully open for approximately 5
seconds to flush the valve seat free of
any debris or sediment.

b) Permit the valve check to snap shut.

c) If lift lever does not activate and there is

no evidence of valve discharge, shut
down equipment immediately and
replace valve.

Illustration shows correct pressure on
gasket

Illustration shows over compressed
gasket

Clean Glass; Replace Gaskets If Leaking

Remove cap at cross section; clean nipple
to boiler

Inspect handholes for scale or sludge

buildup

25

Maintenance

Electric IOM

Advertising