SECTION 3

FTHC-IOM-2012-1001

OPERATION

3-15

!

WARNING

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

4

CAUTION

Do NOT leave unit unattended in
Manual Operation, in this mode the
LMV51 will ignore its internal Set Point.

» 52: Ignition position (after main burner ignition)

» 72: Air damper in the postpurge position

» 76: Traveling to the FGR position

7. Press

Escape 4 times to get back to the main menu.

8. Under

ManualOperation > Setload, change the load to 0% by using the

arrow keys. Press Enter and verify the 0% has been acknowledged in the
curr” fi eld.

9. Press

Escape once to get back to the ManualOperation menu.

10. Under

Auto/Manual/Off , change the operation to Burner On by using the

arrow keys. Press enter and verify that “Burner On” is acknowledged in the
current fi eld.

11. Press

Escape twice to get back to the main menu.

12. Turn the main burner switch Local or On position.

13. Increase the set point. Under operation-Heater set point go to setpoint

W1 using the arrow key then press Enter. Change the set point under new,
using the arrows and press Enter. The new set point should appear under
actual and displayed in degrees.

14. After several seconds the burner control will start its pre-ignition phase

and the blower will start.

15. You can observe the status of the burner by going to the main menu (by

pressing Escape) then selecting Operational Stat > Normal Operation.

16. The unit will purge then drive to the ignition position and the pilot should

light.

17. The burner control will stay at this pilot hold stage so you can inspect and

adjust the pilot as needed.

18. The pilot gas pressure should match the test fi re sheet.

19. The

fl ame signal should be greater than 90% when viewed from the top

menu of the Siemens AZL display.

20. Once the pilot is adjusted properly and you are ready to light the main

burner, press Escape to the main menu.

SETTING MAIN BURNER IGNITION

1. Under

Params&Display >RatioControl >ProgramStop, change the

Program Stop to 52 Interv2. This is the main burner ignition position.
Press Enter and confi rm that 52 Interv2 is acknowledged in the current
fi eld. This change moves the control to the main burner ignition point in
the burner sequence.

2. This will allow the main burner to ignite. Should the burner not light, the

gas and air servo motors are not synchronized to produce a combustible
mix.