Mx series boiler service / maintenance schedule – Lanair MXB360 User Manual

Page 31

Advertising
background image

Visit our website at: www.lanair.com

31

Section 18 - Service / Maintenance

DAILY

• Check fuel supply tank

level.

• Check vacuum gauge

reading on suction line.
See Section 19.

• Check atomizing air pres-

sure at the air filter/ regu-
lator. Set to 12 psi. Drain
water from the bowl if
necessary

• Check the fuel pressure

gauge on the burner. set
to the correct pressure
for the fuel being used.

• Visually inspect flame.

Adjust accordingly.

• Check draft using a

manometer. Set draft to -
.02 cold, -.06 hot.

• If boiler is not to be used

for an extended period
of time, flip the pre-
heater rocker switch off
(light off ).

WEEKLY

• Drain water/ anti-freeze

from the fuel supply
tank.

• Check the air pressure

setting on the primary air
regulator. Set to 30 psi.

• Drain water from the air

pressure supply line
drain leg and primary
regulator.

MONTHLY

• Check the combustion

chamber flue passages.
Clean if needed (see
page 32).

• Clean the chimney, chim-

ney connector and baro-
metric damper.

• Clean pump strainer, suc-

tion line strainer and
pick-up tube strainer (pp
33). NOTE: Always prime
pump after cleaning
strainers.

• Check for dirt build-up

on the combustion
blower wheel. Keep
wheel clean.

• Inspect the combustion

chamber, ash build-up,
and flame.

ANNUALLY

(Season Shut Down)

• Shut off main power sup-

ply to boiler.

• Perform monthly serv-

ice/maintenance.

• Flip air/fuel pre-heater

switch off.

• Shut off air supply.

• Remove air/fuel pre-

heater assembly.
Disassemble and clean.
Replace all o-rings (pp.
34, 35).

• Remove air turbulator

and clean (pp. 34, 35).

• Replace nozzle and quad

ring (pp. 34, 35 ,39)

• Replace Ignitor (pp 38).

• Adjust turbulator (pp 38).

• Lubricate all motors fol-

lowing specifications on
the motor rating plate.

• Clean fuel pump

strainer (see pp 33).

• Drain and clean fuel sup-

ply tank.

• Clean combustion blow-

er, axial fan blades and
fan cage

NOTE: ALWAYS WEAR EYE, FACE AND BREATHING PROTECTION AND PROTECTIVE CLOTH-

ING WHEN INSPECTING OR CLEANING CHAMBER OR ADJUSTING FLAME.

!

MX SERIES BOILER SERVICE / MAINTENANCE SCHEDULE

Advertising