Lanair MXB360 User Manual

Page 8

Advertising
background image

2-1/2” Boiler

Supply Connection

CL

CL

CL

8“

2“

16.5”

16.5” min.

8”

8”

16.5”

33”

47.5”

CL

Dimension as per job specifications and local codes

Boiler Vent

Connections

QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:30 pm CST

8

Section 2 - Typical Boiler Room Layout

Section 3 - Boiler Room Air Requirements

Figure 1

1. To ensure safe efficient operation, the boiler system must be supplied with sufficient air for combustion and ventila-

tion (see Fig. 2)

2. Unless properly controlled, avoid the use of forced ventilation, since it can create an undesirable pressure differen-

tial between the boiler room and air source.

3. All boilers located in confined rooms should have free access to ventilation and combustion air from two perma-

nent openings. One opening should terminate within 12" of the ceiling, the other within 12" from the floor
(see Fig. 2). Each opening shall have at least 1 sq. inch free area per 1,000 BTU/HR of burner input. Openings should
freely connect with areas having adequate infiltration of outside air

WARNING: Failure to provide an adequate supply of fresh air for combustion will result
in hazardous operating conditions. Do not use an exhaust fan in the boiler room.

!