Wire reference chart – LOCKSTATE LS-60 Installation Guide User Manual

Page 17

Advertising
background image

PG

16

PG

16

PG

17

Wire Reference Chart

Possible Wires

What They Control

R or V or VR

RH

and RC Single power for HEAT and COOL

RH or 4

RH

Power for HEAT (RH not connected to RC jumper clip removed)

RC

RC

Power for COOL (RH not connected to RC jumper clip removed)

W

W

Heat control

W2

W2

2nd stage HEAT or heat pump auxiliary heat

W3

W3

3rd stage HEAT or 2nd stage of 2 stage auxiliary heat

Y

Y

COOL control or 1st stage compression for heat pump

Y2

Y2

2nd stage COOL control or 2nd stage compression for a heat pump

G or F

G

FAN control

C or X

C

24VAC power (to power thermostat)

NOTE: TRANE uses B for this connection

H

H

External Humidifier

DH

DH

External De-Humidifier

EX

EX

external fresh air baffle

B

B

Heat pump changeover (cool to heat, powered in heat)

O

O

Heat pump changeover (heat to cool, powered in cool)

B and O

IMPORTANT: If there are both B and O wires (Trane pump

products) DO NOT CONNECT B to B terminal, connect B to C

terminal. If not a Trane product tape off B.

E

n/a Emergency heat (do not connect, tape off)

L

n/a System monitor (do not connect, tape off)

T

n/a Outdoor sensor (do not connect, tape off)