Pop-Up Wizard

The Wizard routine will display factory default settings. Each setting will
display for ten seconds. Use the

or

buttons to change the

setting. Settings that are not changed will operate with the values that
are displayed. To fast forward through the Wizard, press Edit Schedule.
The Wizard can be exited by pressing Start/Stop Schedule. This will
save the settings and place the thermostat into operation.

Use this chart to write down the desired settings before applying power.
Settings may vary by model.

Displayed

Details

Default Change To

SCAL

choose °F or °C

°F

_______

CLOC

choose 12 or 24 hour

12

_______

LITE

y = always on, n = off

y

_______

DIFF

differential, set between 0.5 to 3.0 °F
or 0.5 to 1.5 °C

1 °F

_______

DIF2

2nd stage differential,
added to first stage differential

2 °F

_______

DLY2

2nd stage delay, in minutes

20

_______

DLY3

3rd stage delay, in minutes

20

_______

AUTO

auto changeover enable

y

_______

DEDB

auto changeover deadband
in degrees

3 °F

_______

HI

heat setting limit in degrees

90 °F

_______

LO

cool setting limit in degrees

45 °F

_______

VAC HEAT

vacation heat setpoint in degrees

62 °F

_______

VAC COOL

vacation cool setpoint in degrees

85 °F

_______

CHECK

check filter timer in hours

n or OFF

_______

CYCL

compressor short cycle delay in minutes

5

_______

CAL

calibration offset in degrees

0

_______

After the Wizard has configured the thermostat, the settings can be
edited by pressing

and

simultaneously. This will allow you to

change settings.

Factory settings that have not been changed will use the default settings
for operation.