Thermostat Specifications

Operating Voltage

18-30V AC

Maximum Load Current

1 Amp Max per Output Terminal

4 Amp Total Load

Output Type

Latching Relays

Batteries

2 AA Alkaline in Series

Battery Life

2 Years Typical

Ambient Operating Temperature

14 °F (-10 °C) to 122 °F (50 °C)

Storage Temperature

-4 °F (-20 °C) to 140 °F (60 °C)

Operational Mode Chart:

Demand

Conventional

(Non-HP)

Heat Pump

(HP) Elec

Heat Pump

(HP) Gas

First Stage Heat

W1 + G*

Y1 + G + B

Y1 + G + B

Second Stage Heat

W1 + W2 + G*

Y1 + Y2 + G + B

or

Y1 + W2 + G + B

Y1 + Y2 + G + B

or

Y1 + W2 + G + B

Third Stage Heat

N/A

Y1 + Y2 + E +

G + B

or

Y1 + W2 + E +

G + B

E + B

Emergency Heat

N/A

Y1 + G + O

Y1 + G + O

First Stage Cool

Y1 + G

Y1 + Y2 + G + O

Y1 + Y2 + G + O

Second Stage Cool

Y1 + Y2 + G

E + G

E

* G: G is off for Gas, on for Elec