Securitron AQD5B User Manual

Page 5

Advertising
background image

Page 5

P/N 500-30010

Rev. A, 04/13

4. Make AC Power Input Connections

IMPORTANT: VERIFY AC POWER IS OFF
BEFORE MAKING CONNECTIONS


Connect AC power wires as follows:

Black/Positive = L

White/Negative = N

Green/Ground= G

5. Make DC Power Output Connections to Distribution or Accessory Boards

Using 18 to 24 AWG wire, connect the DC OUT Positive (+) terminal to the positive (+) IN terminal on the
distribution board.

Connect the DC OUT Negative (-) terminal to the Negative/Common/C (-) IN terminal on the distribution
board.

It is recommended to pass the wires under the power module board before connecting to the accessory
board in order to maintain separation from battery cables.

6. Make DC Power Output Connections to Devices

Insert wires into terminal block as indicated. Maintain separation from battery cable placement by at least
1/4”.

Note: Use appropriate wire gauge for the Amperage
and distance of the run.
For more info, see Wire Loss Calculator at

http://www.securitypower.com/AN2Wire.html

Connect the Positive wire to DC OUT Positive (+) terminal
Connect the Negative wire to DC OUT Negative (-) terminal

7. Wiring for Status Monitoring Options

The diagram shows basic wiring to provide output to a control panel or local
alarm for notification of AC power loss.

AC-ON state energized the NO/C switch.

The Switch changes state when power is lost.

Negative

Positive

NO

C NC

AC Fail

Access Control