Connecting the battery, Recommended annual maintenance – Securitron AQD5B User Manual

Page 7

Advertising
background image

Page 7

P/N 500-30010

Rev. A, 04/13

2. Connecting the Battery

Plug battery cable assembly into battery backup plug -BAT+ as shown.

Install batteries. Mark batteries with “Installed” date and “Replace By”
date according to manufacturer’s battery life recommendations.

Connect leads to batteries.

For 12VDC operation:
Connect red battery lead to the Positive (+) battery terminal.
Connect black battery lead to the Negative (-) battery terminal.



For 24VDC operation:
Using Battery Jumper Cable, connect the Positive (+) battery
terminal of one battery to the Negative (-) terminal of the
second battery.

Connect red battery lead to the unused Positive (+) battery terminal.
Connect black battery lead to the unused Negative (-) battery terminal.







Recommended Annual Maintenance

Battery Test

Turn off AC power

Check DC output voltage under battery operation.

For fully charged batteries, voltage should be above 11.5V. If voltage is below this range, test batteries
per battery manufacturer instructions and replace if needed.

AC Fail Test

Turn off AC power. AC Fail switch should trigger an alert upon disconnect or upon fail over to battery
power.

Problems with installation? Call Securitron: 1-800-MAG-LOCK

For warranty information visit: www.securitron.com/en/site/securitron/About/MagnaCare-Warranty

Connect red battery lead to the

unused Positive (+) battery
terminal.

Connect black battery lead to

the unused Negative (-) battery

terminal.

Batteries

Jumper Cable

Advertising