FIRElink-NANO Air Sampling Detector – Installation and User Manual

Page 21 of 21

© 2010 Hochiki Europe (UK) Ltd 9-5-0-425/ISS1/JUL10

13 Technical Data

NOTE: Some devices such as sounders and beacons have high inrush currents on activation, which can

damage relay contacts. It is good practice to consider fitting a suitable current limiting resistor in
series with the load to avoid this potential problem.

SELV Rating

EN 60950 Class III

Supply Voltage.

21.6v – 26.4v DC

Current Consumption

350mA

Electrical Safety

Complies with EN 610190-1

Size (mm)

190w x 230h x 110d

Weight 1.2kg

Operating Temperature Range.

0°C to 38°C (UL 268)
-10°C to 60°C (EN 54-20)

Operating Humidity Range

0 to 90% relative humidity, non-condensing
EN61010-1 Pollution Degree 1
EN61010-1 Installation Category II

IP Rating

IP50

Sensitivity Range

0.4% to 25% obscuration/metre

Detection Principle

Laser light forward scattering mass detection

Maximum Number of Sampling
Holes

Class A: 2
Class B: 4
Class C: 10

Maximum Sampling Pipe
Length

50m

Sampling Pipe Inlets

2 off 3/4” pipe inlets (sampling pipe and exhaust)

Alarm / Fault Relays

Pre Alarm / Fire / Fault

Relay Contact Rating
(Changeover)

1A at 24V DC (resistive load)

Programming

Internal DIL switches

PC Interrogation.

Via optional Communications Card

APIC Compatible

Yes