4 installation: mechanical – Hochiki FIRElink-NANO User Manual

Page 8

Advertising
background image

Page 8 of 21

FIRElink-NANO Air Sampling Detector – Installation and User Manual

© 2010 Hochiki Europe (UK) Ltd 9-5-0-425/ISS1/JUL10

4 Installation:

Mechanical

Cable Entries



2x 20mm Conduit Holes, for example
for 20mm packing glands.



Drilling guides are provided for drilling
two additional 2x 20mm holes in the
top and 1x 20mm hole in the bottom if
needed.

Pipe Entries



¾” ABS Pipe.



Use a ¾” male to 25mm female
adaptor if 25mm pipe is used.

Note: Do not glue pipes into the detector, to
allow for future removal.

Fixing Holes (3 x M5 x 13 slots)

Refer to the printable drilling template on next page for accurate positioning.

NOTE: Ensure the detector is fixed to a flat surface – otherwise the enclosure will twist and may be

damaged.