IAI America E-Con User Manual

Page 89

Advertising
background image

81

5. T

abletop Robot TT

No.

Error name

Contents and Treatment

D5D

Fieldbus error
(FBRS link error)

This occurs when the network connection is not established.
1) Check the station number, the parameters for

communication speed and parameters on PLC side.

2) It is concerned the startup of XSEL is faster than that of

PLC.
Change the settings in I/O Parameter No. 120.
[Refer to Section 4.3 (8) for the details.]

D5E

Fieldbus error
(Mail BOX response)

A communication board error was detected.
Reboot the XSEL controller. If the same error occurs again,
please contact us.

D5F

Network I/F Module Class Mismatch
Error

The setting of I/O Parameter No. 225 Network I/F Module
Class does not match with that of the communication board
currently mounted to XSEL.
Check the contents of the settings in I/O Parameter No. 225,
and in case no doubt is found, please contact us.

D75

Fieldbus Parameter Error

There is an error in a parameter.
Check I/O Parameter No. 226 to 227 and 237 to 238.
Example)

• A node address out of the range was set.

• A communication speed out of the range is set.

D77

Fieldbus error (Exception)

A communication board error was detected.
Reboot the XSEL controller. If the same error occurs again,
please contact us.

E1F

I/O Assignment Parameter Error

It is a parameter setting error.
Check to see that a number out of the I/O port number (except
for -1) is not set to I/O Parameters No. 2 to 9, a number out
of indication is not input to I/O port start number, or a number
out of indication is not input to I/O Parameters No. 14 to 17.
[Refer to XSEL Controller Instruction Manual.]

E20

I/O Duplication Assignment Error

I/O assignment is duplicated.
Check to see that a number out of the I/O port number (except
for -1) is not set to I/O Parameters No. 2 to 9, a number out
of indication is not input to I/O port start number, or a number
out of indication is not input to I/O Parameters No. 14 to 17.
[Refer to XSEL Controller Instruction Manual.]
Check the number of the ports that I/O boards are mounted.

E21

I/O Assignment Number Overflow
Error

I/O assignment has exceeded the specified range.
Check to see that a number out of the I/O port number (except
for -1) is not set to I/O Parameters No. 2 to 9, a number out
of indication is not input to I/O port start number, or a number
out of indication is not input to I/O Parameters No. 14 to 17.
[Refer to XSEL Controller Instruction Manual.]
Check the number of the ports that I/O boards are mounted.

E8F

Fieldbus logic error

It is a logic error at the Fieldbus initializing.