77

5.9 Zone Signal Output

Example of use in operation) While the actuator is moving a zone signal is output inside the zone enclosed by

distances of 40 mm and 120 mm from the home. (40 mm

 Zone signal output 

120 mm)

Method) Use the parameters “Zone boundary+” and “Zone boundary–” to set the zone in

which the zone signal is output, as shown below:

Zone boundary+

120

Zone boundary–

40

RCS controller







































P

L

C

[5] [2]



[1]














[9]



[8] [3]

[7] [6]




[10] [4]

PIO

Signal name

Start

Command position 1

Command position 2

Command position 4

Command position 8

* Pause

Reset

Servo ON

Completed position 1

Completed position 2

Completed position 4

Completed position 8

Position complete

Home return completion

Zone

* Alarm

* Emergency stop

Moving

Category

Input
















Output


Reference flow

Select/enter a desired command position.

[1]

[2]







[3]

[4]

[5]

[6]

[7]

[8]

[9]

[10]

Start input ON

Completed position OFF

Position complete output OFF

Moving output ON

Start input OFF

Moving output OFF

Movement to the selected position
completes.

Position complete output ON

Completed position is output.

Movement to the selected position starts.

Actuator enters the zone. Zone output ON

Actuator exits the zone. Zone output
OFF