SR Heating Cable Selection and Design

Use table 1 to select the heating cable size for insulated metal pipes and use table 2 to select heating cables for

insulated plastic pipes. Read across the table to find the pipe size, then drop down the column to the row

corresponding to the lowest design air temperature column for the application and chose the thickness of the

insulation that will be used. The cell that intersects will give the power (watts/ft.) of the cable required and it may also

have a number (2) in the cell which represents using 2 cables. Run the cable straight along the bottom of the pipe. If
two cables are required, attach them at the 4 and 8 o’clock positions as shown in figure 1 page 4. Spiral tracing the
cable is not recommended as it is labor intensive.

Lowest

Air Temp.

Insulation

Thickness

1/2”

3/4”

1”

1-

1/4”

1-

1/2”

2”

2-

1/2”

3”

4”

6”

8”

0ºF

(-18ºC)

1/2”

3

3

3

3

5

5

5

5

8

8

10

1”

3

3

3

3

3

3

3

5

5

8

8

1-

1/2”

3

3

3

3

3

3

3

3

5

5

5

2”

3

3

3

3

3

3

3

3

3

5

5

-20ºF

(-29ºC)

1/2”

3

5

5

5

5

5

8

8

10

10

*

1”

3

3

3

3

3

5

5

5

8

8

10

1-

1/2”

3

3

3

3

3

3

3

5

5

8

8

2”

3

3

3

3

3

3

3

3

5

5

8

-40ºF

(-40ºC)

1/2”

5

5

5

5

8

8

10

(2) 8

(2) 8

(2) 10

*

1”

3

3

3

5

5

5

8

8

8

10

(2) 8

1-

1/2”

3

3

3

3

3

5

5

5

8

8

10

2”

3

3

3

3

3

3

3

5

5

8

8

3”

3

3

3

3

3

3

3

3

3

5

5

Lowest

Air Temp.

Insulation

Thickness

1/2”

3/4”

1”

1-

1/4”

1-

1/2”

2”

2-

1/2”

3”

4”

6”

8”

0ºF

(-18ºC)

1/2”

3

5

5

5

8

8

8

10

(2) 8

(2) 10

*

1”

3

3

3

5

5

5

5

5

5

8

8

1-

1/2”

3

3

3

3

3

3

5

8

8

8

10

2”

3

3

3

3

3

3

3

5

5

8

8

-20ºF

(-29ºC)

1/2”

5

5

8

8

10

10

(2) 8

(2) 8

(2) 10

*

*

1”

3

3

5

5

5

8

8

8

10

(2) 8

(2) 10

1-

1/2”

5

5

5

5

5

5

5

8

8

10

(2) 8

2”

3

3

3

3

3

5

5

5

8

8

10

-40ºF

(-40ºC)

1/2”

8

8

8

8

10

10

(2) 8

(2) 10

*

*

*

1”

5

5

5

8

8

8

10

10

(2) 8

*

*

1-

1/2”

5

5

5

5

5

8

8

8

10

(2) 8

(2) 10

2”

5

5

5

5

5

5

5

8

8

10

(2) 8

3”

3

3

5

5

5

5

5

5

5

8

10

Table 1'

– SR cable selection for metal pipes (w/ft.)

Table 2'

– SR cable selection for plastic pipes (w/ft.)

'

The tables are based on a using fiberglass insulation or equivalent while maintaining a 40ºF (4ºC) pipe

temperature with a 10% safety factor and 20 mph wind speed.

* Contact King for the proper cable selection

Rev 11.04.12