King Electric SR self-reg, cut to length User Manual

Page 4

Advertising
background image

Model

Volts

Watt/ft

Maximum

Single Run Length

SR123

120V

3 w/ft

325 ft. (99M)

SR243

240V

3 w/ft

650 ft. (198M)

SR125

120V

5 w/ft

270 ft. (82M)

SR245

240V

5 w/ft

540 ft. (165M)

SR128

120V

8 w/ft

210 ft. (64M)

SR248

240V

8 w/ft

420 ft. (128M)

SR1210

120V

10 w/ft

180 ft. (55M)

SR2410

240V

10 w/ft

360 ft. (110M)

Model

240V 208 V 220 V 277V

SR243

3.0

2.5

2.7

3.4

SR245

5.0

4.3

4.6

5.5

SR248

8.0

7.0

7.44

8.6

SR2410

10.0

9.0

9.4

10.5

Volts

Start up

Temp.

Circuit

Breaker*

SR123

3w/ft.

SR125

5w/ft.

SR128

8w/ft.

SR1210

10w/ft.

120 V

50ºF (10ºC)

15 Amp

325 ft. (99M)

225 ft. (69M)

145 ft. (44M)

115 ft. (35M)

20 Amp

435 ft. (133M)

270 ft. (82M)

195 ft. (59M)

150 ft. (46M)

30 Amp

655 ft. (200M)

450 ft. (138M)

290 ft. (88M)

230 ft. (70M)

40 Amp

875 ft. (267M)

540 ft. (164M)

390 ft. (188M)

300 ft. (92M)

0ºF

(-18ºC)

15 Amp

230 ft. (70M)

155 ft. (47M)

100 ft. (30M)

85 ft. (26M)

20 Amp

305 ft. (93M)

205 ft. (72M)

130 ft. (40M)

110 ft. (34M)

30 Amp

460 ft. (140M)

310 ft. (94M)

195 ft. (59M)

155 ft. (47M)

40 Amp

615 ft. (188M)

410 ft. (144M)

260 ft. (80M)

220 ft. (68M)

-20ºF

(-29ºC)

15 Amp

205 ft. (63M)

135 ft. (41M)

90 ft. (27M)

75 ft. (23M)

20 Amp

275 ft. (84M)

180 ft. (55M)

115 ft (35M)

100 ft. (30M)

30 Amp

415 ft. (127M)

270 ft. (82M)

175 ft. (53M)

145 ft. (44M)

40 Amp

555 ft. (169M)

360 ft. (110M)

230 ft. (70M)

200 ft. (60M)

Volts

Start up

Temp.

Circuit

Breaker*

SR243

3w/ft.

SR245

5w/ft.

SR248

8w/ft.

SR2410

10w/ft.

240 V

50ºF (10ºC)

15 Amp

650 ft. (198M)

460 ft. (140M)

295 ft. (90M)

230 ft. (70M)

20 Amp

865 ft. (264M)

540 ft. (165M)

390 ft. (119M)

305 ft. (93M)

30 Amp

1300 ft. (396M)

920 ft. (280M)

590 ft. (180M)

460 ft. (140M)

40 Amp

1725 ft. (529M)

1080 ft. (330M)

780 ft. (238M)

610 ft. (186M)

0ºF

(-18ºC)

15 Amp

460 ft. (140M)

310 ft. (94M)

200 ft. (61M)

165 ft. (50M)

20 Amp

615 ft. (188M)

415 ft. (127M)

265 ft. (81M)

220 ft. (67M)

30 Amp

925 ft. (282M)

620 ft. (189M)

395 ft. (120M)

325 ft. (99M)

40 Amp

1235 ft. (377M)

830 ft. (254M)

420 ft. (128M)

440 ft. (134M)

-20ºF

(-29ºC)

15 Amp

410 ft. (125M)

275 ft. (84M)

175 ft. (53M)

150 ft. (46M)

20 Amp

545 ft. (166M)

379 ft. (113M)

235 ft (72M)

195 ft. (59M)

30 Amp

820 ft. (250M)

540 ft. (165M)

350 ft. (107M)

290 ft. (83M)

40 Amp

1095 ft. (334M)

758 ft. (226M)

420 ft. (128M)

390 ft. (118M)

Table 3: Maximum Single Cable Length

Table 4: Wattage Adjustment (W/Ft)

The maximum length of a single cable run is noted in Table 3
and cannot be exceeded. If the application requires a longer
cable run, then multiple cables and additional power circuits
must be used.

When using 240 volt SR cable on 208, 220 or 277 volt
applications, the power output (wattage) must be adjusted.
Refer to Table 4 for the adjusted watts/ft of the cable when
operated at a voltage other than 240 volt.

Circuit protection depends on the length of cable required
and the start-up temperature since the cable will draw more
power (wattage) when cold. Multiple cables can be run from
a single power circuit up to a maximum combined length as
noted in Table 5. Larger amperage circuits breakers can
handle longer combined cable lengths, but the maximum
length for a single cable run does not change. The NEC
requires the use of ground fault protection breakers for
heating cable.

NOTE: 240 volt cable lengths in Table 5 are also good for
208, 220, and 277 volt.

Table 5: Circuit Protection Per Combined Cable Length for Pipe Freeze Protection

Circuit Breaker Protection and Cable Length Design for Pipe Freeze Protection

Rev 11.04.12

www.king-electric.com

4