Staub Electronics EP-400-NMC EPISODE - RACK MOUNT UPS NETWORK MANAGMENT CARD User Manual

Page 12

Advertising
background image

Remote Management System

12

[UPS->Master Switch] Switches the output power of the UPS to be on or off.

Items

Definition

Reboot UPS

Turns the UPS off and back on

Turn UPS Off

Turns the UPS off.

UPS Sleep

Turning the UPS off and back on after a period of
time.

Cancel Switch

Cancels a pending action to turn the UPS off.

Turn UPS On

Turns the UPS on.

Shutdown Delay

Length of time the UPS waits before it turns off in
response to a "Reboot UPS", "Turn UPS off" or "UPS
Sleep" command.

Reboot Duration

After the UPS is turned off, Reboot Duration defines
how long the UPS waits before its turned back on in
response to "Reboot UPS" command.

Sleep Duration

After the UPS is turned off, Sleep Duration defines
how long the UPS waits before it is turned back on in
response to "Sleep UPS" command.

Signal Clients to Shutdown

Select this option to warn PowerPanel Business
Edition Clients before UPS turning off.
The Shutdown Delay for the UPS can be revised to
insure a graceful shutdown.



[UPS->Diagnostics] When a power failure occurs, the UPS immediately supplies battery power
to all connected equipment. The UPS must have sufficient runtime for all connected computers
to be shut down properly.
The UPS/Diagnostics page provides the ability to verify the UPS can supply adequate battery
runtime for the connected computers to shutdown properly. Perform a complete runtime
calibration to ensure an accurate estimate of the runtime for the connected load.

Battery Test

The Battery Test performs a battery test to verify the batteries are good and provides
information on the battery, including the results and date of the last battery test. Click the Initiate
button to begin a battery test.
Performing a battery test is prohibited when the Frequency Working Mode option is set to fixed.
If performing a battery test on the fixed frequency mode, a UPS fault may occur and cause the
UPS to enter bypass mode. The frequency on bypass mode may not be acceptable and damage
the connected equipment.
The results will be reported after a battery test completes:

Last Test Date: The date the last battery test was performed.
Last Test Result: The results of the last battery test:

Advertising