System Sensor SPS and SPSV series Wall and Ceiling speaker_strobes User Manual

System Sensor Equipment

Advertising
background image

spectralert advance sps and spsv series
Wall and Ceiling speaker/strobes for
fire protective signaling systems

insTaLLaTion and mainTenanCe insTruCTions

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTICE: This manual shall be left with the owner/user of this equipment.
The “K” models are suitable for outdoor use in wet environments with out-
door back box supplied with the product.
generaL desCripTion
The SpectrAlert Advance series of notification appliances offers a wide range
of speaker/strobe products for wall and ceiling applications, indoors and out-
doors. The strobe portion is designed to be used in 12 or 24 volt, DC or FWR
(full wave rectified) systems. The speaker portion can be operated with distri-
bution amplifiers having an output voltage of either 25 or 70.7 volts.

With its low total harmonic distortion, the SpectrAlert Advance SP series of-
fers high fidelity sound output. The SpectrAlert Advance SPV series offers
greater sound output at every tap setting for applications with high ambient
noise levels. The speakers operate at any one of four input power levels. These
products are electrically backward compatible with the previous generation of
SpectrAlert notification appliances. All SpectrAlert Advance products are suit-
able for use in synchronized systems. The System Sensor MDL3 module may
be used to provide synchronization for the strobes. Wall and ceiling products
may be used interchangeably (wall products may be used on the ceiling and
ceiling products may be used on the wall.) K Series products are designed to
be used over a wider range of temperatures and are suitable for use in wet

SS-140-001

1 I56-3109-011R

For use with models:
SPSR, SPSRH, SPSW, SPSWH, SPSRV, SPSWV, SPSRK, SPSWK, SPSCR, SPSCRH, SPSCW, SPSCWH, SPSRHK, SPSCRV,
SPSCRVH, SPSCWV, SPSCWVH, SPSCWK, SPSCWHK, SPSR-P, SPSRH-P, SPSW-P, SPSWH-P, SPSRV-P, SPSWV-P,
SPSCW-P, SPSCWH-P, SPSCWVH-P, SPSCHWV-P, SPSRK-P, SPSWK-P, SPSCW-CLR-ALERT, SPSW-CLR-ALERT,
SPRK-R, SPWK-R, SPSWK-R, SPSRK-R, SPSCWHK-P, SPSWK-CLR-ALERT, SPSCWK-CLR-ALERT
NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates
NOTE: When replacing outdoor units; device and back box must be replaced

locations.
fire aLarm sYsTem ConsideraTions
All wiring must be installed in compliance with the National Electrical Code
(NEC) and applicable local codes. System Sensor recommends installing fire
alarm speakers in compliance with NFPA 72, ANSI/UL1480 and NEC 760.
Loop design and Wiring
The system designer must make sure that the total current drawn by the de-
vices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage. The
current draw information for making these calculations can be found in the
tables within this manual. For convenience and accuracy, use the voltage drop
calculator on the System Sensor website (www.systemsensor.com) or CD-ROM.

When calculating the voltage available to the last device, it is necessary to
consider the voltage drop due to the resistance of the wire. The thicker the
wire, the smaller the voltage drop. Wire resistance tables can be obtained from
electrical handbooks. Note that if Class A wiring is installed, the wire length
may be up to twice as long as it would be for circuits that are not fault tolerant.

NOTE: For 24 volt applications, the total number of strobes on a single NAC
must not exceed 40, with a maximum loop resistance of 120 ohms. For 12 volt
applications, the total number of strobes must not exceed 12, with a maxi-
mum loop resistance of 30 ohms.

I56-3

109-0
11R

produCT speCifiCaTions

Operating Temperature

Standard

32°F to 120°F (0°C to 49°C) K Series –40°F to 151°F (–40°C to 66°C)

Humidity Range

Standard

10% to 93% Non-condensing K Series Meets NEMA 4X, IP56 rating requirements

Nominal Voltage (speakers)

25 Volts or 70.7 Volts (nominal)

Max. Supervisory Voltage (speakers and strobes)

50 VDC

Strobe Flash Rate

1 flash per second

Nominal Voltage (strobes)

Regulated 12VDC or FWR or regulated 24DC or FWR

Speaker Frequency Range

400 to 4000 Hz

Power Settings (Speakers)

1

/

4

,

1

/

2

, 1, 2 watts

Operating Voltage Range
(includes fire alarm panels with built in sync)

8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)

Operating Voltage with MDL3 Sync Module

8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)

Input Terminal Wire Guage

12-18 AWG

Dimensions for Speaker/Strobes and Accessories

NOTE: V suffix denotes high volume device, C suffix denotes ceiling device.

Wall Product

Length Width

Depth

Ceiling Product

Diameter

Depth

SPS Speaker/Strobe

6.0˝

5.0˝

4.7˝ (including lens and speaker) SPSC Speaker/Strobe

6.8˝

4.7˝ (including lens and speaker)

SPSV Speaker/Strobe

6.0˝

5.0˝

4.8˝ (including lens and speaker) SPSCV Speaker/Strobe

6.8˝

4.8˝ (including lens and speaker)

Weatherproof back box **

6.5˝

5.5˝

2.9˝*

Weatherproof back box **

7.2˝

2.9˝*

Surface Mount Skirt

6.5˝

5.0˝

2.7˝*

Surface Mount Skirt

7.2˝

2.7˝*

*Depth above finished surface of wall or ceiling. **Weatherproof back box dimensions do not include the two mounting tabs.

Mounting Box Options

2-Wire Indoor Products

K Series Products

4 Ч 4 Ч 2

1

/

8

or deeper

MWBB - red wall metal weatherproof back box
MWBBW - white wall metal weatherproof back box
MWBBCW - white ceiling metal weatherproof back box

The indoor SP and SPV Series are suitable for dry and damp environments. The “K” Series models are suitable for use in both indoor and outdoor applications.