System Sensor SPS and SPSV series Wall and Ceiling speaker_strobes User Manual

Page 2

Advertising
background image

TabLe 1. sound LeveLs for eaCh Transformer poWer Tap:

UL Reverberant (dBA @ 10 ft.)

SPS, SPSC

SPSV, SPSCV

2W

85

89

1W

82

86

1

/

2

W

79

83

1

/

4

W

76

80

CAUTION

Signal levels exceeding 130% rated signal voltage can damage the speaker.
Consequently, an incorrect tap connection may cause speaker damage. This
means that if a 25V tap is selected when a 70.7V amplifier is being used,
speaker damage may result. Therefore, be sure to select the proper taps for the
amplifier voltage/input power level combination being used.

TabLe 2. sTrobe CurrenT draW measuremenTs:

Strobe Current Draw(mA)

Candela

8-17.5 Volts

16-33 Volts

DC

FWR

DC

FWR

Standard Candela Range

15

123

128

66

71

15/75

142

148

77

81

30

NA

NA

94

96

75

NA

NA

158

153

95

NA

NA

181

176

110

NA

NA

202

195

115

NA

NA

210

205

High Candela Range

135

NA

NA

228

207

150

NA

NA

246

220

177

NA

NA

281

251

185

NA

NA

286

258

CandeLa seLeCTion
Adjust the slide switch on the rear of the product to position the desired can-
dela setting in the small window on the front of the unit. All products meet
the light output profiles specified in the appropriate UL Standards. Use Table 2
to determine the current draw for each candela setting. For K series products
used outdoors at low temperatures, listed candela ratings must be reduced in
accordance with Table 3.

NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V op-
erating voltages when set to any other candela settings.
TabLe 3. CandeLa deraTing:

Listed Candela Rating

Candela rating at -40°F (K Series Outdoor Applications Only)

15

Do not use

below 32°F

15/75

30

75

44

95

70

110

110

115

115

135

135

150

150

177

177

185

185

NOTE: Supply power for strobe must be continuous for proper operation.
figure 1. Wiring diagram:

INPUT FROM

AMPLIFIER

INPUT FROM

POWER

SUPPLY

OUTPUT TO

NEXT SPEAKER

OR EOL

OUTPUT TO

NEXT STROBE

OR EOL

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

A0388-00

eLeCTriCaL Wiring
1. Connect the speaker as shown in Figure 1.

NOTE: Do not loop electrical wiring under terminal screws. Wires con-
necting the device to the control panel must be broken at the device
terminal connection in order to maintain electrical supervision.

2. There are two rotary switches on the back of the product The first switch

is used to select either 25 or 70.7 volts input for the speaker portion. The
second switch is used to select the input power of

1

/

4

,

1

/

2

, 1 or 2 watts.

See diagram.

shorTing spring
NOTE: Shorting springs are provided between terminals 2 and 3 and between
terminals 5 and 6 of the mounting plate to enable wiring checks after the
system has been wired, but prior to installation of the final product. These
springs will automatically disengage when the product is installed, to enable
supervision of the final system.
figure 2. shorTing spring

SHORTING SPRINGS

A0391-00

figure 3. speaker WaTTage and voLTage seTTings:

A0419-00

SS-140-001

2 I56-3109-011R

UL Anechoic (dBA @ 10 ft.)

SPS, SPSC

SPSV, SPSCV

2W

88

93

1W

86

90

1

/

2

W

83

87

1

/

4

W

80

84

Advertising